Product Name: |
Low frequency Inverter LW1000-6000W |
Mode No. : |
LW1000,LW2000,LW3000,LW5000,LW6000 |
Classification: |
Low frequency Inverter |
Introduction: |
Based on transformer technology,strong loading capacity.Used for all kinds of home/office equipments,solar power system. |
Main Features
1. LCD digital display show voltage, load and battery info in real time.
2. Peak power is three times of rated power.
3. Can work with inductive load such as air conditioner, motor door and so on.
4. Pure sine wave output, available for sensitive load.
5. 4-step progressive charging, 7 battery type selector.
6. Fast and powerful charger with 20A/35A/50A/70A/90A.
7. Accept generator’s energy output.
8. High power factor 1.0, low power consumption.
9. Automatically transfer between battery and line modes.
10.Microprocessor control guarantees high reliability.
11.Remote control function.
12.Protection against: Over load, over temperature, over charging, low battery.
Model
|
LW1000
|
LW2000
|
LW3000
|
LW4000
|
LW5000
|
LW6000
|
AC Input
|
Nominal Power |
1000W
|
2000W
|
3000W
|
4000W
|
5000W
|
6000W
|
Voltage |
120VAC/230VAC
|
230VAC
|
Acceptable Voltage |
194-243VAC/164-243VAC(wide mode)
|
Line low Transfer |
85V±4%/184(154 wide mode±4% )
|
Line low Return |
95V±4%/194(164 wide mode±4% )
|
Line high Transfer |
135V±4%/253±4%
|
Line high Return |
127V±4%/243±4%
|
Frequency |
50Hz or 60Hz (auto sensing)
|
Line low Transfer |
47Hz for 50Hz, 57Hz for 60 Hz
|
Line high Transfer |
55Hz for 50Hz, 65Hz for 60 Hz
|
Out Input
|
Phase &waveform |
Pure Sine Wave(bypass mode sync to input)
|
Voltage |
100/110/120/130VAC, 208/220/230/240VAC (bypass mode sync to input)
|
Voltage Regulation |
±10%rms(bypass mode sync to input)
|
Frequency |
50Hz±0.3Hz(bypass mode sync to input)
|
Peak Power |
3 times of rating power
|
Short Circuit Protection |
Yes, shutdown after 10ms
|
Power Factor |
0.9-1.0
|
DC Input
|
Battery Voltage |
12V/24V/48V
|
24V/48V
|
Minimum Start Voltage |
10V for 12V, 20V for 24V, 40V for 48V
|
Low Battery Alarm |
10.5V for 12V, 21V for 24V, 42V for 48V
|
Low Battery Transfer |
10V for 12V, 20V for 24V, 40V for 48V
|
High Voltage Alarm |
16V for 12V, 32V for 24V,64V for 48V
|
Max Charging Current |
20A/35A/70A/90A
|
Over charge Voltage |
15.7V for 12V,31.4V for 24V, 62.8V for 48V
|
Transfer Efficiency
|
Line Mode |
>95%
|
Battery Mode |
>88%
|
Power saver |
Available when the load is less than 25 Watts
|
Indicators
|
Switch selector |
Saving Mode is on/off when push the switch forwards/backwards , Keeping it horizontal is turning the inverter off.
|
Audible Alarm |
Sounding when the heatsink’s tem is over 105℃ and shutdown after 30 seconds.
|
Protections |
low battery/ over charging /over temp/over load
|
Communications |
RS-232/USB(custom-made)
|
Enviromental
|
Operating Environment |
0-40℃,0-90%℃ RH(non-condensing)
|
Audible Noise |
<60dB
|
Net Weight (KG) |
18
|
20
|
22
|
35
|
38
|
40
|
Dimension(LxWxH) |
446×218×179mm
|
605×218×179mm
|
Product specifications are subject to change without further notice,the form is only for reference,please make the specific parameters as the standard.