UPS ZLPOWER 3 pha vào 3 pha ra, sử dụng Modul Nguồn
93M SERIES MODULAR ONLINE UPS 25-600KVA (380V/400V/415V)
The 93M series modular UPS provides the mostcompact footprint of less than 2m' with maximumcapacity of 900kVA.With best reliability and highperformance, it has been leading the domesticmarket for years.
Features:
Each power module has an independent LCD, gives users’ direct overview of status data and alarms in real time
Provide graphical and text based information of alarms, status data, instructions that users can have more friendly and safer operation
High power density, footprint for 300kVA is 0.66m², power density 409kW/m², saving valuable data center space
Scalable from 30kVA to 900kVA, max 30 power modules in parallel
Smart Sleep function can intelligently make some power modules go to sleep when load is relatively low, improving the efficiency of the remaining power modules and saving customers on power and cooling costs.
Improving efficiency ,reducing power and cooling costs
Easy setting with just two steps. Customers can select sleep mode and rotation period
Power modules working in rotation, prolong the life time
Specification:
Model
|
93M600/30X
|
93M300/30X
|
93M180/30X
|
System Capacity
|
600KVA
|
300KVA
|
180KVA
|
Power Module Capacity
|
30KVA/27KW
|
30KVA/27KW
|
30KVA/27KW
|
Input
|
Dual Input
|
Optional
|
Phase
|
3 Phase+Neutral+Ground, 380V/400V/415V(line-line)
|
Input Voltage Range
|
304~478Vac (line-line),full load; 228V~304Vac (line-line),load decreases linearly according to the min phase voltage
|
Rate Frequency
|
50/60Hz
|
Input Frequency Range
|
40Hz~70Hz
|
Bypass
|
Input PF
|
>0.99
|
Input THDi
|
< 3% (100% Linear Load) |
Rate Voltage
|
380/400/415VAC (line-line)
|
Rate Frequency
|
50/60Hz
|
Input Voltage Range
|
Settable, -40%~+25%
|
Output
|
Bypass Frequency Range
|
Settable, ±1Hz, ±3Hz, ±5Hz
|
Bypass Overload
|
110% long term operation; 125% for 5 mins ;150% for 1 min; 400% for 1s
|
Rate Voltage
|
380/400/415VAC (line-line)
|
Voltage Regulation
|
1% for balance load; 1.5% for unbalance load
|
Rate Frequency
|
50/60Hz
|
Frequency Precision
|
0.1%
|
Output PF
|
0.9
|
|
Output THDu
|
< 1%, Linear Load; < 5.5%, Non-Linear Load |
Crest Factor
|
3:1
|
Battery
|
Inverter Overload
|
110% for 1 hour; 125% for 10 mins ;150% for 1 min; >150% for 200 ms
|
Voltage
|
±240VDC
|
Battery Number
|
40pcs (Settable: even number from 32 to 44)±1%
|
Voltage Precision
|
Charge Power
|
up to 20% * Output active power
|
Battery Cold Start
|
Standard
|
Efficiency
|
AC Mode
|
95.5%
|
ECO Mode
|
99.0%
|
Battery Mode
|
95.0%
|
System
|
Display
|
10.4" color touch screen LCD + LED + keyboard
|
IP Class
|
IP 20
|
Interface
|
RS232,RS485, Programmable Dry Contact, USB
|
Option
|
SNMP Card, Parallel kit, SPD, LBS,Dust filter, Expansion dry contact card
|
Temperature
|
Operation: 0~ 40 ℃ Storge: -40 ~70 ℃
|
Relative Humidity
|
0 ~95% Non-condensing
|
Altitude
|
< 1000m. Within 1000m to 2000m, power derate 1% for every 100m rise |
Noise (1 meter)
|
72dB@100%load 65dB@100%load 65dB@100%load 65dB@45%load 62dB@45%load 62dB@45%load
|
|
Applicable Standards
|
040-1-1 EMC: IEC/EN 62040-2 Performance: IEC/EN 62040-3
|
Physical
|
Weight (kg)
|
Cabinet
|
660
|
220
|
165
|
Power module
|
34
|
34
|
34
|
Dimension W*D*H(mm)
|
Cabinet
|
2000*1050*2000
|
600*1100*2000
|
600*1100*1600
|
Power module
|
460*790*134
|
460*790*134
|
460*790*134
|